2 fault detection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 133

Advertising
background image

Digital Operator Display

Fault Name

Control circuit terminals have

shorted out (+V, AC).

• Check for wiring errors along the control circuit terminals.
• Correct the wiring.
Check the resistance of the speed potentiometer and related wiring.

Control terminal input current has

exceeded allowable levels.

• Check the input current.
• Reduce the current input to control circuit terminal (+V) to 20 mA.

Digital Operator Display

Fault Name

CPF03

PWM Data Error
There is a problem with the PWM data.

Cause

Possible Solution

Drive hardware is damaged.

Replace the drive.

Digital Operator Display

Fault Name

CPF06

EEPROM Data Error
There is an error in the data saved to EEPROM.

Cause

Possible Solution

Control circuit is damaged.

Cycle power to the drive. If the problem continues, replace the drive.

The power supply was switched off

when parameters were written (e.g.,

using a communications option

card).

• Cycle power to the drive and check operation again.
• Initialize the drive using A1-03.
• If the problem persists after initializing the drive, replace the drive.

Digital Operator Display

Fault Name

CPF07

Terminal Board Communications Error
A communication error occurred at the terminal board.

Cause

Possible Solution

There is a fault connection between

the terminal board and control

board.

Turn the power off and reconnect the control circuit terminals.

Digital Operator Display

Fault Name

CPF08

EEPROM Serial Communication Fault
EEPROM communications are not functioning properly.

Cause

Possible Solution

Terminal board or control board is

not connected properly.

Turn the power off and check the control terminal connections.

5.2 Fault Detection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

133

5

Troubleshooting