Safe Disable Input Precautions

u

Safe Disable Function Description

The Safe Disable function can be utilized to perform a safe stop according to the IEC/EN

61800-5-2, stop category 0 (Uncontrolled stop by power removal). It is designed to meet the

requirements of the ISO/EN 13849-1, Safety Category 3, PL d, and IEC/EN 61508, SIL2.
Removing the voltage from terminal H1 disables the drive output, i.e. the power supply to the

motor is cut by stopping the switching of the output transistors in a safe way. “Hbb” is shown

on the display. Safe Disable is applicable for induction and permanent magnet motors.

u

Installation

If the Safe Disable function is utilized, the wire link between the terminals HC and H1 that is

installed at shipment must be removed entirely.
Connect the drive to an ISO/EN 13849-1, Safety Category 3 interrupting device so that in case

of a Safe Disable request the connection between the terminals HC and H1 is opened.

Power Supply

Controller

HC

H1

ISO/EN 13849-1 Safety
Cat, 3 Device

M

Drive

Figure C.9 Safe Disable Wiring Example

C.3 Safe Disable Input Precautions

234

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

Advertising