Setting 3: exhaust fan application – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 98

Advertising
background image

No.

Parameter Name

No.

Parameter Name

b1-02

Run Command Selection 1

L3-04 Stall Prevention Selection during

Deceleration

C1-01 Acceleration Time 1

u

Setting 3: Exhaust Fan Application

Table 4.7 Exhaust Fan: Parameter Settings

No.

Parameter Name

Default Setting

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Prohibited

C6-01

Drive Duty Selection

1: Normal Duty

E1-03

V/f Pattern Selection

0FH

E1-07

Middle Output Frequency

30.0 Hz

E1-08

Middle Output Frequency Voltage

50.0 V

L2-01

Momentary Power Loss Operation Selection 1: Enabled

L3-04

Stall Prevention Selection during

Deceleration

1: Enabled

Table 4.8 Exhaust Fan: User Parameters (A2-01 to A2-16)

No.

Parameter Name

No.

Parameter Name

b1-01

Frequency Reference Selection 1

E1-07 Middle Output Frequency

b1-02

Run Command Selection 1

E1-08 Middle Output Frequency Voltage

b1-04

Reverse Operation Selection

E2-01 Motor Rated Current

b3-01

Speed Search Selection at Start

H1-05 Multi-Function Digital Input Terminal

S5 Function Selection

C1-01 Acceleration Time 1

H1-06 Multi-Function Digital Input Terminal

S6 Function Selection

C1-02 Deceleration Time 1

H1-07 Multi-Function Digital Input Terminal

S7 Function Selection

E1-03 V/f Pattern Selection

L5-01 Number of Auto Restart Attempts

4.5 Application Selection

98

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide