T1-04: motor rated current – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 121

Advertising
background image

n

T1-04: Motor Rated Current

Used to set the motor rated current according to the motor nameplate value. For optimal

performance in OLV, the motor rated current should be between 50 and 100% of the drive

rating. Enter the current at the motor base speed.

No.

Name

Setting Range

Default

T1-04

Motor Rated Current

10 to 200% of drive

rated current

Determined

by o2-04 and

C6-01

n

T1-05: Motor Rated Frequency (T1-01 = 0 or 3)

Used to set the motor rated frequency according to the motor nameplate value. If a motor with

an extended speed range is used or the motor is used in the field weakening area, enter the

base frequency here.
For higher tuning precision and better control performance, enter the motor no-load frequency

here if known. The “no-load frequency” refers to the frequency needed to operate the motor

under no-load condition at its rated speed. Refer to the motor data sheet.

No.

Name

Setting Range

Default

T1-05

Motor Base Frequency

0.0 to 400.0 Hz

60.0 Hz

n

T1-06: Number of Motor Poles (T1-01 = 0 or 3)

Used to set the number of motor poles according to the motor nameplate value.

No.

Name

Setting Range

Default

T1-06

Number of Motor Poles

2 to 48

4

n

T1-07: Motor Base Speed (T1-01 = 0 or 3)

Used to set the motor rated speed according to the motor nameplate value. If a motor with an

extended speed range is used or the motor is used in the field weakening area, enter the speed

at base frequency here.

No.

Name

Setting Range

Default

T1-07

Motor Base Speed

0 to 24000 r/min

1750 r/min

4.7 Auto-Tuning

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

121

4

Start-Up Programming & Operation