Auto-tuning example, Set the selected type of auto-tuning – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 117

Advertising
background image

5.

Start the Auto-Tuning process when prompted by the drive.

6.

If Auto-Tuning was successfully performed, do a test run without the load and make any

necessary parameter adjustments.

7.

If the test run was successful, do a test run with the load connected and make parameter

adjustments if necessary.

u

Auto-Tuning Example

The following example illustrates how to perform Rotational Auto-Tuning for Open Loop

Vector Control (A1-02 = 2).

n

Set the Selected Type of Auto-Tuning

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

2.

Press the

key until the Auto-Tuning display appears.

3.

Press

to begin setting parameters.

4.

Press

to display the value for T1-01.

5.

Press

to select the digit to edit.

6. Press

and set the drive to perform Rotational Auto-Tuning

(00).

7.

Save the setting by pressing

.

8. The display automatically returns to the display shown in Step 3.

4.7 Auto-Tuning

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

117