5.3

Alarm Detection

u

Alarm Codes, Causes, and Possible Solutions

Table 5.3 Alarm Codes, Causes, and Possible Solutions

Digital Operator Display

Minor Fault Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside the acceptable setting range.

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

bUS

Option Communication Error
• After initial communication was established, the connection was lost.
• Assign a Run command frequency reference to the option card.

CALL

Serial Communication Transmission Error
Communication has not yet been established.

CE

MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

CrST

Can Not Reset

CyC

MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.

dEv

Speed Deviation (for Simple V/f with PG)
According to the pulse input (RP), the speed deviation is greater than the setting in

F1-10 for a time longer than the setting in F1-11.

dnE

Drive Disabled

E5

MECHATROLINK Watchdog Timer Error

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for over 0.5 s.

EF0

Option Card External Fault
An external fault condition is present.

EF1

External fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External fault (input terminal S3)
External fault at multi-function input terminal S3.

5.3 Alarm Detection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

153