2 fault detection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 145

Advertising
background image

Digital Operator Display

Fault Name

Cause

Possible Solution

Load is too heavy.

Reduce the load.

Cycle times are too short during

acceleration and deceleration.

Increase the settings for the acceleration and deceleration times (C1-01 through

C1-08).

Voltage is too high for the V/f

characteristics.

• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve

reducing E1-08 and E1-10.

• Be careful not to lower E1-08 and E1-10 excessively because this reduces load

tolerance at low speeds.

Drive capacity is too small.

Replace the drive with a larger model.

Overload occurred when operating

at low speeds.

• Reduce the load when operating at low speeds.
• Replace the drive with a model that is one frame size larger.
• Lower the carrier frequency (C6-02).

Excessive torque compensation.

Reduce the torque compensation gain (C4-01) until there is no speed loss but less

current.

Speed Search related parameters

are not set correctly.

• Check the settings for all Speed Search related parameters.
• Adjust the current used during Speed Search and the Speed Search deceleration

time (b3-03 and b3-02 respectively).

• After Auto-Tuning the drive, enable the Speed Search Estimation Type (b3-24

= “1”).

Output current fluctuation due to

input phase loss

Check the power supply for phase loss.

Digital Operator Display

Fault Name

oL3

Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer

than the allowable time (L6-03).

Cause

Possible Solution

Parameter settings are not

appropriate for the type of load.

Check the settings of parameters L6-02 and L6-03.

There is a fault on the machine side

(e.g., the machine is locked up).

Check the status of the load. Remove the cause of the fault.

Digital Operator Display

Fault Name

oL4

Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for

longer than the allowable time (L6-06).

Cause

Possible Solution

Parameter settings are not

appropriate for the type of load.

Check the settings of parameters L6-05 and L6-06.

5.2 Fault Detection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

145

5

Troubleshooting