Output terminals, 5 control circuit wiring – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 69

Advertising
background image

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Main

Frequency

Reference

Input

RP Multi-function pulse train input (frequency

reference)

Response frequency: 0.5 to 32 kHz

(Duty Cycle: 30 to 70%)

(High level voltage: 3.5 to 13.2 Vdc)

(Low level voltage: 0.0 to 0.8 Vdc)

(input impedance: 3 kΩ)

+V Analog input power supply

+10.5 Vdc (max allowable current 20 mA)

A1 Multi-function analog input 1 (frequency

reference)

Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000

A2 Multi-function analog input 2 (frequency

reference)

Input voltage or input current (Selected by DIP switch

S1 and H3-09) 0 to +10 Vdc (20 kΩ),

Resolution: 1/1000

4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),

Resolution: 1/500

AC Frequency reference common

0 Vdc

n

Output Terminals

Table 3.7 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function
Digital Output

<1>

MA N.O. (fault)

Digital output

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA (reference value)

MB N.C. output (fault)
MC Digital output common

Multi-Function

Photocoupler

Output

P1 Photocoupler output 1 (During run)

Photocoupler output 48 Vdc, 2 to 50 mA

<2>

P2 Photocoupler output 2 (Frequency agree)

PC Photocoupler output common

Monitor Output

MP Pulse train output (Output frequency)

32 kHz (max)

<3>

<4>

AM Analog monitor output

0 to 10 Vdc (2 mA or less) Resolution: 1/1000

AC Monitor common

0 V

<1>

Do not assign functions to digital relay outputs that involve frequent switching. This may shorten relay
performance life. Switching life is estimated at 200,000 times (assumes 1 A, resistive load).

<2>

Connect a suppression diode as shown in

Figure 3.14

when driving a reactive load such as a relay coil. Ensure

the diode rating is greater than the circuit voltage.

<3>

When set for sourcing. +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher.

<4>

When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.

3.5 Control Circuit Wiring

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

69

3

Electrical Installation

Advertising