A.4 drive specifications – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 171

Advertising
background image

Item

Specification

Control

Character-

istics

Functions

Momentary Power Loss Ride-Thru

Speed Search

Over/Undertorque Detection

Torque Limit, Multi-Step Speed (17 steps max)

Accel/Decel Time Switch

S-Curve Accel/Decel,

2-Wire/3-Wire Sequence

Rotational Auto-Tuning

Stationary Auto-Tuning of Line-to-Line Resistance

Dwell

Cooling Fan ON/OFF

Slip Compensation

Torque Compensation

Jump Frequencies (reference dead band)

Frequency Reference Upper/Lower Limit

DC Injection Braking (start and stop), High Slip Braking

PID Control (with Sleep Function)

Energy Saving

MEMOBUS/Modbus (RS-485/RS-422 Max 115.2 kbps)

Fault Reset

Parameter Copy

DriveWorksEZ

Fault Restart

Removable Terminals with Parameter Backup Function

Protection

Functions

Motor Protection

Motor overheat protection via output current sensor

Overcurrent Protection

Drives stops when output exceeds 200% of the rated current (Heavy

Duty)

Overload Protection

A stop command will be entered after operating at 150% for 60 s
(Heavy Duty)

<4>

Overvoltage Specification

200 V Class: Stops when DC bus voltage exceeds approx. 410 V

400 V Class: Stops when DC bus voltage exceeds approx. 820 V

Low Voltage Protection

Drive stops when DC bus voltage falls below the levels indicated:

<5>

190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase

400 V), 350 V (3-phase 380 V)

Momentary Power Loss Ride-

Thru

3 selections available: Ride-Thru disabled (stops after 15 ms), time base

of 0.5 s, and continue running as long as the drive control board is
powered up.

<6>

Heatsink Overheat Protection

Protected by thermistor

Braking Resistor Overheat

Protection

Overheat input signal for braking resistor (Optional ERF-type, 3% ED)

Stall Prevention

Stall prevention is available during acceleration, deceleration, and

during run. Separate settings for each type of stall prevention determine

the current level at which stall prevention is triggered.

Cooling Fan Failure Protection

Circuit protection (“fan-lock” sensor)

Ground Fault Protection

Electronic circuit protection

<7>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

A.4 Drive Specifications

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide