B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 196

Advertising
background image

No.

Name

Description

H3-14 Analog Input Terminal Enable

Selection

Determines which analog input terminal or terminals will be enabled

when a digital input programmed for “Analog input enable” (H1-

 = C) is activated.

1: Terminal A1 only

2: Terminal A2 only

7: All terminals enabled

Note: Available in drive software versions PRG: 1016 and later.

H3-16 Terminal A1 Offset

Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16

until the monitor U1-13 for the terminal A1 input voltage reads 0.0%.

The process is the same for terminal A2.

Note: Available in drive software versions PRG: 1016 and later.

H3-17 Terminal A2 Offset

Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17

until the monitor U1-14 for terminal A2 input voltage reads 0.0%.

Note: Available in drive software versions PRG: 1016 and later.

H3 Multi-Function Analog Input Settings

H3-

Setting

Function

Maximum Input Level Possible

0

Frequency Bias

Max output frequency (E1-04).

1

Frequency Gain

Frequency reference (voltage)

2

Auxiliary Frequency Reference (used as multi-step speed 2)

Max output frequency (E1-04)

4

Output Voltage Bias

200 V Class: 200 V

400 V Class: 400 V

7

Overtorque/Undertorque Detection Level

Open Loop Vector: Motor rated torque

V/f control: Drive rated current

B

PID Feedback

10V = 100%

C

PID Set Point

10V = 100%

E

Motor Temperature (PTC input)

10 V = 100.00%

F

Not used/Through Mode

10

FWD Torque Limit

Motor rated torque

11

REV Torque Limit

Motor rated torque

12

Regenerative Torque Limit

Motor rated torque

15

FWD/REV Torque Limit

Motor rated torque

16

Differential PID Feedback

10 V = 100%

30/31

DriveWorksEZ Analog Input 1/2

These settings are for analog output

functions used in DriveWorksEZ.

Normally there is no need to change or

apply these settings.

41

Output Voltage Gain

Note: Function available in versions PRG: 1016 and later.

10 V = 100.00%

B.1 Parameter Table

196

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

Advertising