5 control circuit wiring, Control circuit terminal block functions, Refer to – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 68: Terminal board, Control circuit wiring, Input terminals

Advertising
background image

3.5

Control Circuit Wiring

u

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S1 to

S7), multi-function digital outputs (MA, MB), multi-function pulse inputs and outputs (RP,

MP) and multi-function photocoupler outputs (P1, P2). The default is called out next to each

terminal in

Figure 3.1

.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being

wired. Operating a drive with untested control circuits could result in death or serious injury.

WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter

A1-06 may change the I/O terminal function automatically from the factory setting.

Refer to Application

Selection on page 96

. Failure to comply may result in death or serious injury.

n

Input Terminals

Table 3.6 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-

Function

Digital

Inputs

S1 Multi-function input 1 (Closed: Forward

run, Open: Stop)

Photocoupler

24 Vdc, 8 mA

Note: Drive preset to sinking mode. When using

source mode, set DIP switch S3 to allow for a 24 Vdc

(±10%) external power supply.

Refer to Sinking/

Sourcing Mode Switch on page 74

.

S2 Multi-function input 2 (Closed: Reverse

run, Open: Stop)

S3 Multi-function input 3 (External fault

(N.O.)

S4 Multi-function input 4 (Fault reset)

S5 Multi-function input 5 (Multi-step speed

reference 1)

S6 Multi-function input 6 (Multi-step speed

reference 2)

S7 Multi-function input 7 (Jog reference)

SC Multi-function input common (Control

common)

Sequence common

Safe

Disable

Input

HC Power supply for safe disable input

+24 Vdc (max 10 mA allowed)

Do not use external power supply.

H1 Safe disable input

Open: Output disabled

Closed: Normal operation

Note: Disconnect wire jumper between HC and H1

when using the safe disable input. The wire length

should not exceed 30 m.

Use only dry contacts on safety inputs HC-H1.

3.5 Control Circuit Wiring

68

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

Advertising