3 alarm detection – Yaskawa J1000 Compact Vector Control Drive User Manual
Page 156
Advertising
Digital Operator Display
Minor Fault Name
Uv
Undervoltage
One of the following conditions was true when the drive was stopped and a run
command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was open.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is
not 0 and DC bus voltage is under L2-05.
5.3 Alarm Detection
156
YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide