Yaskawa J1000 Compact Vector Control Drive User Manual

Page 54

Advertising
background image

<2>

The MC on the input side of the main circuit should open when the thermal relay is

triggered.

<3>

Self-cooled motors do not require separate cooling fan motor wiring.

<4>

Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink

mode (0 V com).

<5>

Use only a +24 V internal power supply in sinking mode; the source mode requires

an external power supply.

Refer to I/O Connections on page 74

for details.

<6>

Monitor outputs work with devices such as analog frequency meters, ammeters,

voltmeters and wattmeters; they are not intended for use as a feedback-type of signal.

<7>

Disconnect the wire jumper between HC and H1 when utilizing the safety input.

Refer

to Wiring Procedure on page 72

for details on removing the jumper. The wire length

for the Safe Disable input should not exceed 30 m. Use only dry contacts on safety

inputs HC-H1. External power supplies are not permitted.

<8>

Note that if the drive is set to trigger a fault output whenever the fault restart function

is activated (L5-02 = 1), then a sequence to interrupt power when a fault occurs will

result in shutting off the power to the drive as the drive attempts to restart itself. The

default setting for L5-02 is 0 (fault output active during restart attempt).

WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction

input terminal parameter is properly set (S5 for 3-Wire; H1-05 = “0”). Improper sequencing of run/stop circuitry

could result in death or serious injury from moving equipment.

WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the

correct state before energizing the drive. Failure to comply could result in death or serious injury from moving

equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive

to start.

WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control

terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up (default).

If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is

set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of

the drive and may cause injury.

WARNING! When the application preset function is executed (or A1-06 is set to any value other than 0) the

drive I/O terminal functions change. This may cause unexpected operation and potential damage to

equipment or injury.

Figure 3.2

illustrates an example of a 3-Wire sequence.

Drive

Sequence input common

Run relay (N.O.)

Stop relay (N.C.)

Run command (run on momentary close)

Stop command (stop on momentary open)

Forward/reverse command
(multi-function input: H1-05 = 0)

S1

S2

S5

SC

Figure 3.2 3-Wire Sequence

3.1 Standard Connection Diagram

54

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide