2 fault detection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 152

Advertising
background image

Digital Operator Display

Fault Name

Problem with the CHARGE

indicator.

Replace the drive.

Digital Operator Display

Fault Name

Uv2

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Cause

Possible Solution

L2-02 changed from its default

value in drive that is 7.5 kW or

smaller without installing a

Momentary Power Loss Ride-

Thru.

Correct parameter L2-02 setting or install optional Momentary Power Loss Ride-

Thru unit.

The wiring for the control power

supply is damaged.

• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.

Internal circuitry is damaged.

• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.

Digital Operator Display

Fault Name

Uv3

Undervoltage 3 (Inrush Prevention Circuit Fault)
The inrush prevention circuit has failed.

Cause

Possible Solution

The contactor on the inrush

prevention circuit is damaged.

• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Check monitor U4-06 for the performance life of the inrush prevention circuit.
• Replace the drive if U4-06 exceeds 90%.

5.2 Fault Detection

152

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide