Setting 4: hvac fan application, Setting 5: compressor application – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 99

Advertising
background image

u

Setting 4: HVAC Fan Application

Table 4.9 HVAC Fan: Parameter Settings

No.

Parameter Name

Default Setting

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Prohibited

C6-01

Drive Duty Selection

1: Normal Duty

C6-02

Carrier Frequency Selection

3: 8.0 kHz

H2-03

Terminals P2 Function Selection

39: Watt Hour Pulse Output

L2-01

Momentary Power Loss Operation

Selection

2: CPU Power Active - Drive will restart if

power returns prior to control power supply

shut down.

L8-03

Overheat Pre-Alarm Operation Selection 4: Operation at lower speed

L8-38

Carrier Frequency Reduction

2: Enabled across entire frequency range.

Table 4.10 HVAC Fan: User Parameters (A2-01 to A2-16)

No.

Parameter Name

No.

Parameter Name

b1-01

Frequency Reference Selection 1

E1-03 V/f Pattern Selection

b1-02

Run Command Selection 1

E1-04 Maximum Output Frequency

b1-04

Reverse Operation Selection

E2-01 Motor Rated Current

C1-01 Acceleration Time 1

H3-11 Terminal A2 Gain Setting

C1-02 Deceleration Time 1

H3-12 Terminal A2 Bias Setting

C6-02 Carrier Frequency Selection

L2-01 Momentary Power Loss Operation

Selection

d2-01

Frequency Reference Upper Limit

L8-03 Overheat Pre-Alarm Operation Selection

d2-02

Frequency Reference Lower Limit

o4-12

kWh Monitor Initialization

u

Setting 5: Compressor Application

Table 4.11 Compressor: Parameter Settings

No.

Parameter Name

Default Setting

A1-02

Control Method Selection

0: V/f Control

b1-04

Reverse Operation Selection

1: Reverse Prohibited

C1-01

Acceleration Time 1

5.0 s

C1-02

Deceleration Time 1

5.0 s

C6-01

Drive Duty Selection

0: Heavy Duty

4.5 Application Selection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

99

4

Start-Up Programming & Operation