3 alarm detection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 155

Advertising
background image

Digital Operator Display

Minor Fault Name

oH2

Drive Overheat Warning
“Drive Overheat Warning” was input to a multi-function input terminal, S1 through

S7 (H1-= B)

oH3

Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded

the alarm level (H3-02 or H3-10 = E).

oL3

Overtorque 1
Drive output current (or torque in OLV) was greater than L6-02 for longer than the

time set in L6-03.

oL4

Overtorque 2
Drive output current (or torque in OLV) was greater than L6-05 for longer than the

time set in L6-06.

oL5

Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.

oS

Overspeed (for Simple V/f with PG)
Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting.

ov

DC Bus Overvoltage
The DC bus voltage exceeded the trip point.

For 200 V class: approximately 410 V

For 400 V class: approximately 820 V (740 V when E1-01 < 400)

PASS

MEMOBUS/Modbus Comm. Test Mode Complete

PGo

PG Disconnect (for Simple V/f with PG)
Detected when no PG pulses received for a time longer than setting in F1-14.

rUn

Motor Switch during Run
A command to switch motors was entered during run.

SE

MEMOBUS/Modbus Communication Test Mode Error

TrPC

IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.

UL3

Undertorque Detection 1
Drive output current (or torque in OLV) less than L6-02 for longer than L6-03 time.

UL4

Undertorque Detection 2
Drive output current (or torque in OLV) less than L6-05 for longer than L6-06 time.

5.3 Alarm Detection

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

155

5

Troubleshooting