Yaskawa J1000 Compact Vector Control Drive User Manual

Page 102

Advertising
background image

The table below shows how to set up the drive when using output terminals P2-PC as brake

control output.

Brake Open/Close

Brake Activation Level

Control Mode

Function

Parameter

Signal

Parameter

V/f

OLV

OLV

for PM

Frequency

Detection 2

L4-07 = 0

Frequency Detection Level

L4-01 = 1.0 to 3.0 Hz

<1>

O

O

H2-03 = 5

Frequency Detection Width

L4-02 = 0.0 to 0.5 Hz

<2>

<1>

This is the setting recommended when using Open Loop Vector Control. In V/f Control, set the level as the
motor rated slip frequency plus 0.5 Hz. Not enough motor torque will be created if this value is set too low, and
the load may tend to slip. Make sure this value is greater than the minimum output frequency and greater than
the value of L4-02 as shown in the diagram below. If set too high, however, there may be a jolt at start.

<2>

Hysteresis for Frequency Detection 2 can be adjusted by changing the Frequency Detection Width (L4-02)
between 0.0 and 0.5 Hz. If the load slips during stop, make changes in steps of 0.1 Hz until the load no longer
slips.

L4-02

L4-01

OFF

ON

Time

Output
frequency

Frequency
detection 2

Figure 4.8 Frequency Detection 2

The braking sequence should be designed as follows:
• A normally open signal (N.O.) should be used to control the brake so that it is released

when terminal P2-PC closes.

• When an Up or Down command is entered, the brake should release.
• When a fault signal is output, the brake should close.

• When changing the speed using an analog signal, make sure that the source of the frequency

reference is assigned to the control circuit terminals (b1-01 = 1).

• A sequence to open and close the holding brake appears in the diagram below.

4.5 Application Selection

102

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

Advertising