A.2 single/three-phase 200 v class drives – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 167

Advertising
background image

Table A.3 Power Ratings Continued

Item

Specification

Three-Phase Model

2A0030

2A0040

2A0056

2A0069

Single-Phase Model

<1>

-

-

-

-

Maximum Motor Size Allowed (HP)

<2>

ND Rating

7.5/10.0

10.0

20.0

25.0

HD Rating

7.5

10.0

15.0

20.0

Input

Input Current

(A)

<3>

Three-

Phase

ND Rating

37.0

52.0

68.0

80.0

HD Rating

24.0

37.0

52.0

68.0

Single-

Phase

ND Rating

-

-

-

-

HD Rating

-

-

-

-

Output

Rated Output Capacity

(kVA)

<4>

ND Rating

11.4

15.2

21.3

26.3

HD Rating

9.5

12.6

17.9

22.9

Output Current (A)

ND Rating

<5>

30.0

40.0

56.0

69.0

HD Rating

25.0

<6>

33.0

<6>

47. 0

<6>

60.0

<6>

Overload Tolerance

ND Rating: 120% of rated output current for 1 minute

HD Rating: 150% of rated output current for 1 minute

(Derating may be required for applications that start and

stop frequently)

Carrier Frequency

User-adjustable 2 to 15 kHz

Max Output Voltage (V)

Three-phase power: 200 to 240 V

Single-phase power: 200 to 240 V

(both proportional to input voltage)

Max Output Frequency (Hz)

400 Hz (user-adjustable)

Power

Supply

Rated Voltage

Rated Frequency

Three-phase power: 200 to 240 V 50/60 Hz

Single-phase power: 200 to 240 V 50/60 Hz

DC power supply: 270 to 340 V

<7>

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Harmonic Corrective

Actions

DC Link Choke

Optional

<1>

Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor.

<2>

The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.

<3>

Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.

<4>

Rated motor capacity is calculated with a rated output voltage of 220 V.

<5>

Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier
frequency.

<6>

Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.

<7>

DC is not available for UL standards.

A.2 Single/Three-Phase 200 V Class Drives

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

167

A

Specifications

Advertising