10 test run checklist – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 127

Advertising
background image

No.

Checklist

Page

10

The

should illuminate after giving a run command.

11

To give a run command and frequency reference from the LED Digital Operator, press

to set to LOCAL. The LO/RE key lights while LOCAL is displayed.

88

12

If the motor rotates in the opposite direction during the test run, switch two of the drive

output terminals (U/T1, V/T2, W/T3).

95

13

Select the correct duty rating (C6-01) for the application.

14

Set the correct values for the motor rated current (E2-01) and the motor protection

selection (L1-01) to ensure motor thermal protection.

15

If the run command and frequency reference are provided via the control circuit

terminals, set the drive for REMOTE and be sure the LO/RE light is out.

88

16

If the control circuit terminals should supply the frequency reference, select the correct

voltage input signal level (0 to 10 V) or the correct current input signal level (4 to 20

mA or 0 to 20 mA).

88

17

Set the proper voltage to terminal A1. (0 to 10 V).

18

Set the proper current to terminal A2. (4 to 20 mA or 0 to 20 mA).

19

When current input is used, set H3-09 to “2” (4 to 20 mA) or “3” (0 to 20 mA) and set

H3-10 to “0”.

20

When current input is used, switch the drive built-in DIP switch S1 from the V-side

(OFF) to I-side (ON).

21

Set the minimum and maximum frequency references to the desired values. Make the

following adjustments if the drive does not operate as expected:

Gain adjustment: Set the maximum voltage/current signal and adjust the analog input

gain (H3-03 for input A1, H3-11 for input A2) until the frequency reference value

reaches the desired value.

Bias adjustment: Set the minimum voltage/current signal and adjust the analog input

bias (H3-04 for input A1, H3-12 for input A2) until the frequency reference value reaches

the desired minimum value.

4.10 Test Run Checklist

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

127