2 fault detection – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 150

Advertising
background image

Digital Operator Display

Fault Name

IGBT fault

• Check motor wiring
• Cycle power to the drive.
• If the problem continues, contact your Yaskawa representative or the nearest

Yaskawa sales office.

IGBT short circuit detection and

circuit fault

Digital Operator Display

Fault Name

SEr

Too Many Speed Search Restarts
The number of speed search restarts exceeded the number set to b3-19.

Cause

Possible Solution

Speed Search parameters are set to

the wrong values.

• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).
• Repeat Auto-Tuning.

The motor is coasting in the

opposite direction of the Run

command.

Set b3-14 to 1 to enable Bi-directional Speed Search.

Digital Operator Display

Fault Name

STo

Motor Pull Out or Step Out Detection
Motor pull out or step out has occurred. Motor has exceeded its pull out torque.

Cause

Possible Solution

The wrong motor code has been set

(Yaskawa motors only).

• Enter the correct motor code for the PM being used into E5-01.
• For special-purpose motors, enter the correct data to all E5 parameters

according to the Test Report provided for the motor.

Load is too heavy.

• Increase the value set to n8-55 (Load Inertia for PM).
• Increase the value set to n8-51 (Pull-In Current during Accel/Decel for PM).
• Reduce the load.
• Increase the motor or drive capacity.

Load inertia is too heavy.

Increase n8-55 (Load Inertia for PM).

Acceleration and deceleration

times are too short.

• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Increase the S-curve acceleration and deceleration times (C2-01).

Digital Operator Display

Fault Name

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02)

for longer than the allowable time (L6-03).

Cause

Possible Solution

Parameter settings are not

appropriate for the type of load.

Check the settings of parameters L6-02 and L6-03.

There is a fault on the machine side. Check the load for any problems.

5.2 Fault Detection

150