Grounding, Ce standards compliance for dc power supply input – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 214

Advertising
background image

n

Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the

drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.

n

CE Standards Compliance for DC Power Supply Input

Install the fuses in the following tables to meet CE standards.

M

M

W/T3

Drive

V/T2

U/T1

+1

_

W/T3

Drive

V/T2

U/T1

+1

_

+

_

Fuse

Fuse

DC power supply

(converter)

Figure C.2 Example of DC Power Supply Input (Two Drives Connected in Series)

Note:

1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all

fuses when one fuse blows.

2.

Refer to on page 52

for an AC power supply.

3. The recommended fuses and fuse holders are made by Fuji Electric.

C.1 European Standards

214

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide