background image

Drive

Model

Terminal

Recomm.

Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw

Size

Tightening

Torque

N•m (lb.in.)

4A0018

R/L1, S/L2, T/L3

10

14 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

10

14 to 6

⊖, ⊕1, ⊕2

14 to 6

B1, B2

14 to 10

8

14 to 6

M5

2 to 2.5

(17.7 to 22.1)

4A0023

R/L1, S/L2, T/L3

10

10 to 6

M4

2.1 to 2.3

(18.6 to 20.4)

U/T1, V/T2, W/T3

10

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

14 to 10

8

10 to 6

M5

2 to 2.5

(17.7 to 22.1)

4A0031

R/L1, S/L2, T/L3

8

10 to 6

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

8

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

14 to 10

2.7 to 3.0

(23.9 to 26.6)

6

<1>

10 to 6

M6

5.4 to 6.0

(47.8 to 53.1)

4A0038

R/L1, S/L2, T/L3

6

10 to 6

M5

3.6 to 4.0

(31.8 to 35.4)

U/T1, V/T2, W/T3

8

10 to 6

⊖, ⊕1, ⊕2

10 to 6

B1, B2

10 to 8

2.7 to 3.0

(23.9 to 26.6)

6

10 to 6

M6

5.4 to 6.0

(47.8 to 53.1)

<1>

When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1.

Refer

to EMC Filter Installation on page 216

for details.

Note:

Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a

continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation.

Ambient temperature should not exceed 30 °C.

Closed-Loop Crimp Terminal Recommendations

Yaskawa recommends crimp terminals made by JST and Tokyo DIP for the insulation cap.

Table C.9

matches the wire gauges and terminal screw sizes with Yaskawa-recommended

crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque

Specifications table for the wire gauge and screw size for your drive model. Place orders with

a Yaskawa representative or the Yaskawa sales department.

C.2 UL and CSA Standards

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide