Digital Operator Display

Fault Name

Incorrect PG pulse settings.

Set the H6-02 (Pulse Train Input Scaling) = 100%, the frequency of the PG pulses

at maximum motor speed.

Inappropriate parameter settings.

Check the setting for the overspeed detection level and the overspeed detection

time (F1-08 and F1-09).

Digital Operator Display

Fault Name

ov

Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
• For 200 V class: approximately 410 V
• For 400 V class: approximately 820 V (740 V when E1-01 is less than 400)

Cause

Possible Solution

Deceleration time is too short and

regenerative energy flows from the

motor into the drive.

• Increase the deceleration time (C1-02, C1-04, C1-06, C1-08).
• Install a braking resistor or a dynamic braking resistor unit.
• Enable stall prevention during deceleration (L3-04 = “1”).

Stall prevention is enabled as the default setting.

Fast acceleration time causes the

motor to overshoot the speed

reference.

• Check if sudden drive acceleration triggers an overvoltage alarm.
• Increase the acceleration time.
• Use longer S-curve acceleration and deceleration times.

Excessive braking load.

The braking torque was too high, causing regenerative energy to charge the DC

bus.

Reduce the braking torque, use a braking option, or lengthen decel time.

Surge voltage entering from the

drive input power.

Install a DC link choke.

Note: Voltage surge can result from thyristor convertor and phase advancing

capacitor using same drive main input power supply.

Ground fault in the output circuit

causing the DC bus capacitor to

overcharge.

• Check the motor wiring for ground faults.
• Correct grounding shorts and turn the power back on.

Improper Setting of Speed Search

related parameters. (Includes

Speed Search after a momentary

power loss and after a fault restart.)

• Check the settings for Speed Search related parameters.
• Enable Speed Search Retry function

(b3-19 greater than or equal to 1 to 10).

• Adjust the current level during Speed Search and the deceleration time (b3-02

and b3-03 respectively).

• Perform Line-to-Line Resistance Auto-Tuning and then enable Speed

Estimation Type Speed Search (b3-24 = 1).

Excessive regeneration when

overshoot occurs after acceleration.

• Enable the Overvoltage Suppression function (L3-11 = 1).
• Lengthen the S-curve at acceleration end.

Drive input power voltage is too

high.

• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.

The dynamic braking transistor is

damaged.

Replace the drive.

The braking transistor is wired

incorrectly.

• Check braking transistor wiring for errors.
• Properly rewire the braking resistor device.