Application Precautions

u

General Application Precautions

n

Selecting a Reactor

An AC reactor or DC link choke can be used for the following:
• to suppress harmonic current.
• to smooth peak current that results from capacitor switching.
• when the power supply is above 600 kVA.
• when the drive is running from a power supply system with thyristor converters.

Note:

A DC link choke is built in to 200 V and 400 V class models with a capacity of 22 kW and higher (HD

rating).

4000

600

0

60

400

Drive Capacity (kVA)

Power Supply

Capacity (kVA)

Power supply harmonics
reactor required

Reactor
unnecessary

Figure i.3 Installing a Reactor

n

Drive Capacity

Make sure that the motor rated current is less than the rated nameplate output current of the

drive. When running more than one motor in parallel from a single drive, the drive rated current

should 1.1 times larger than the total motor rated current for all connected motors or nuisance

drive faults may occur.

n

Starting Torque

The overload rating of the drive determines the starting and accelerating characteristics of the

motor. Expect lower running torque than when running the motor from line power. To get

more starting torque, use a larger drive or increase both the motor and drive capacity.