Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit

in the power supply the current flow will not rise above 31,000 amps maximum at 240 V for

200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the

short-circuit tolerance of the power supply being used.

• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical

amperes for 240 V in 200 V class drives (up to 480 V for 400 V class drives) motor overload

protection.

u

CSA Standards Compliance

Figure C.7 CSA Mark

n

CSA for Industrial Control Equipment

The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.

14-05.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload

protection. The internal motor overload protection is UL listed and in accordance with the

NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model Dependent
Default Setting: Model Dependent
Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0

(default is 1, standard induction motor protection enabled).