B.1 parameter table – Yaskawa J1000 Compact Vector Control Drive User Manual

Page 199

Advertising
background image

No.

Name

Description

L2-01

Momentary Power Loss Operation

Selection

0: Disabled - Drive trips on (UV1) fault when power is lost.

1: Power Loss Ride-Thru Time - Drive will restart if power returns

within the time set in L2-02.

2: CPU Power Active - Drive will restart if power returns as long as

the CPU is working.

L2-02

Momentary Power Loss Ride-Thru

Time

Refer to V1000 Technical Manual for details.

L2-03

Momentary Power Loss Minimum

Baseblock Time

Refer to V1000 Technical Manual for details.

L2-04

Momentary Power Loss Voltage

Recovery Ramp Time

Refer to V1000 Technical Manual for details.

L2-05

Undervoltage Detection Level

(UV)

Refer to V1000 Technical Manual for details.

L2-06

KEB Deceleration Time

Refer to V1000 Technical Manual for details.

L2-07

KEB Acceleration Time

Refer to V1000 Technical Manual for details.

L2-08

KEB Start Output Frequency

Reduction

Refer to V1000 Technical Manual for details.

L2-11

Desired DC Bus Voltage during

KEB

Refer to V1000 Technical Manual for details.

L3: Stall Prevention Function

Use L3 parameters to configure the stall prevention function.

L3-01

Stall Prevention Selection during

Acceleration

Refer to V1000 Technical Manual for details.

L3-02

Stall Prevention Level during

Acceleration

Used when L3-01 = 1 or 2.

100% is equal to the drive rated current. Decrease the set value if

stalling or excessive current occurs with default setting.

L3-03

Stall Prevention Limit during

Acceleration

Refer to V1000 Technical Manual for details.

L3-04

Stall Prevention Selection during

Deceleration

0: Disabled

1: General Purpose

2: Intelligent

3: Stall Prevention with Braking Resistor

4: Overexcitation Deceleration

7: Overexcitation Deceleration 3

Note: Setting 7 is available in drive software versions PRG: 1020 and

later.

L3-05

Stall Prevention Selection during

Run

0: Disabled

1: Decel Time 1

2: Decel Time 2

L3-06

Stall Prevention Level during

Run

Enabled when L3-05 is set to “1” or “2”. 100% is equal to the drive

rated current.

L3-11

OV Suppression Function

Selection

Refer to V1000 Technical Manual for details.

L3-17

Overvoltage Suppression and Stall

Prevention Desired DC Bus

Voltage

Refer to V1000 Technical Manual for details.

B.1 Parameter Table

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

199

B

Parameter List