Enter the required information from the motor nameplate. Press

to proceed to the Auto-

Tuning start display.

Note:

These instructions continue from Step 7 in “Enter Data from the Motor Nameplate”.

Step

Display/Result

1.

After setting T1-07 as illustrated in the previous section, press

and confirm the display is as described below:

2.

Press

to activate Auto-Tuning.

flashes.

Note: The first digit indicates which motor is undergoing Auto-Tuning

(motor 1 or motor 2). The second digit indicates the type of Auto-

Tuning being performed.

3. Auto-Tuning finishes in approximately one to two minutes.

u

Input Data for Auto-Tuning

The T1- parameters are used to set the Auto-Tuning input data.

Note:

1. Cycling power to the drive will reset any values set during the Auto-Tuning process to factory

defaults.

2. For motors that are to be operated in the field weakening range, first perform the Auto-Tuning with

the base data, i.e. the frequency at which the motor is operating with its rated voltage (base frequency).

After Auto-Tuning is complete, change the maximum frequency E1-04 to the desired value.

n

T1-00: Motor 1/Motor 2 Selection

Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input is set

for function H1- = 16. This parameter is not displayed if motor 1/2 switching is disabled.

No.

Name

Setting Range

Default

T1-00

Motor 1/2 Selection

1 or 2

1

Setting 1: Motor 1

Auto-Tuning automatically sets parameters E1- and E2- for motor 1.

Setting 2: Motor 2

Auto-Tuning automatically sets parameters E3- and E4- for motor 2. Make sure that

motor 2 is connected to the drive for Auto-Tuning.

4.7 Auto-Tuning

YASKAWA ELECTRIC TOEP C710606 47C YASKAWA AC Drive – V1000 Quick Start Guide

119