ProSoft Technology MVI56-AFC User Manual

Page 115

Advertising
background image

MVI56-AFC ♦ ControlLogix Platform

Events

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 115 of 316

February 25, 2011

9.2

Event Log Structures

The Event Log header contains housekeeping information for maintaining the

Log. Its layout is:

Address

Description

40000

Number of records maximum ( == 1999 )

40001

Next new record position ( 0 thru maximum-1 )

40002

Next new event number ( 0 thru 65535, wrapping to 0 )

40003

Oldest event number on file

40004

Oldest event number on file not yet downloaded

40005-40007

[reserved]


Each event record is an 8-register quantity laid out as four 32-bit items (big-

endian):

Registers

Contents

0 to 1

Event Id Tag (page 116)

2 to 3

Timestamp of event
In our standard "packed bit-field" format.

4 to 5

Old item value
For a Datum Point event, format depends on the "datum type" field of the

Event Id Tag.

6 to 7

New item value
For a Datum Point event, format depends on the "datum type" field of the

Event Id Tag.


Each value is right-justified in its field and sign-extended or padded with zeros (0)

if necessary, according to the source data type.

Advertising