Alarm Message

Description

Solution

Analysis Total Zero
(v ≤ 2.04)

The molar concentration sum is zero. Make sure that the sum of all molar

concentrations is within the error

tolerance of 1.0000 (100%).

Analysis
Characterization
error (v ≥ 2.05)

Absolute difference between analysis
total and 1.0000 (100%) is greater

than the error tolerance, OR the

molar concentration sum is zero.

Make sure that the sum of all molar
concentrations is within the error

tolerance of 1.0000 (100%).
Alarm Code values:
0 = No alarm
1 = Analysis total not normalized
2 = Analysis total zero

Compressibility

calculation error

The compressibility calculation
resulted in error based on the input

values and configuration parameters

used.

Check the input values and meter

configuration parameters.
Alarm Code values:
0 = No alarm
1 = Density exceeded reasonable

maximum (warning only)
2 = Pressure maximum found
3 = Non-convergence of procedure

"braket"
4 = Non-convergence of procedure

"ddetail"

Differential Pressure

Low

The differential pressure value
transferred to the module is below

the DP Alarm Threshold parameter

configured in the Meter

Configuration.

Check the input differential pressure
value transferred to the module. If the

value is correct, change the DP

Alarm Threshold parameter for your

project.

Flow Rate Low

The flow rate value transferred to the
module is below the FR Alarm

Threshold parameter configured in

the Meter Configuration.

Check the input flow rate value
transferred to the module. If the value

is correct, change the FR Alarm

Threshold parameter for your project.

Pulse Frequency

Low

The pulse frequency value
transferred to the module is below

the Frequency Alarm Threshold

parameter configured in the Meter

Configuration.

Check the input pulse frequency
value transferred to the module. If the

value is correct, change the

Frequency Alarm Threshold

parameter for your project.

High Water error

Set if input water content is greater
than 99% (less than 1% oil). For this

condition, the emulsion is deemed to

be all water. Both volume and mass

fractions are set to zero. The module
does not perform any density

correction calculation, so the "default

standard density" value is assumed.

This alarm is applied for emulsion

liquids only.

Check that the value of process input

"Water %" is reasonable
Alarm Code values:
0 = No alarm
1 = Emulsion is more than 99% water

Input Out of Range

The input value is not within the
range specified in the meter

configuration window. Applies to

temperature, pressure, differential

pressure, flowing density, water
content, pulse frequency (v ≥ 2.05).

Check that the input variable's

ranges (Meter Configuration /
Process Input
button) and the
process input itself have reasonable

values.