Special Notes

Monitoring Bit 0 (R) of the Block ID Element of the Input Function Block

 This bit is set to 1 if a Pass-Through Modbus message from a SCADA host

was present.

 This bit is set to 0 if no message was present.

Monitoring Bit 1 (B) of the Block ID Element of the Input Function Block

 This bit is set to 1 if the Modbus message from a SCADA host was a bit write

- Modbus function code 5 or 15.

 This bit is set to 0 if the Modbus message from a SCADA host was a word

write - Modbus function codes 1 or 16.

Monitoring Bit 2 (W) of the Block ID Element of the Input Function Block

 This bit is set to 1 if the Modbus message from the SCADA host was longer

than the data block size you defined - Overflow Status.

 This bit is set to 0 if the Modbus message from a SCADA host was

successfully transferred to the controller (or flushed).

Note: Refer to Function Block Structure (page 168) for information on Bit 8 and 9 settings.


Function 4 is the same as function 6, except that the received command remains

pending even if no overflow occurred; this allows you to "pre-inspect" the

command before completing its processing with function 6. Functions 5 and 7 are

the same as functions 4 and 6 respectively, except that for word-write commands

(Modbus function codes 6 and 16) pairs of words in the data are swapped.

11.2.5 Function Block Definition - 8: Meter Process Variables