ProSoft Technology MVI56-AFC User Manual

Page 158

Advertising
background image

Security (Passwords)

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 158 of 316

ProSoft Technology, Inc.

February 25, 2011

The Accessed Port and Authorization register is a bit-mapped word defined as

follows:

Bits

Description

0 to 3

The number of the accessing port (0 for Modbus Gateway)

4

Read Authorization Waived

5

Write Authorization Waived

6

Read Access Granted

7

Write Access Granted

8 to 15

Reserved


A waived authorization means that password entry is not required for this action

even if a non-zero password has been configured. Authorization waivers are

configured separately for each port, so, for example, a SCADA system

connected to port 2 can be allowed to read measurement results without having

to supply a password while an operator connecting AFC Manager to port 1 still

must enter the correct password. The backplane is always given both waivers, so

the PLC never has to supply a password.

To set a hard password in AFC Manager:

1 Open the Site Configuration Dialog box
2 Click in the Site Options field. This action opens the Site Options dialog box
3 Select (check) option 4, Hard Passwords

When this option is selected, any authorization granted using Hard Passwords

times out after two minutes of inactivity, and the user will be required to re-enter

the password to continue.

Advertising
This manual is related to the following products: