MVI56-AFC ♦ ControlLogix Platform

Meter Channel Functionality

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 39 of 316

February 25, 2011

3.6.8 Process Input Scaling

The module allows you to either pre-scale the process inputs via ladder logic for

use in the measurement calculations, or provide unscaled values from the analog

input modules directly. In the second case, the scaling is done internally. You can

directly enter the zero-scale, the full-scale, and the default values for each of the

process variable inputs through the configuration window. Pre-scaled values may

be transferred as floating point or as scaled integer.
When selecting scaled integer, the integer values are scaled as follows:

Scaled Integer

Variable

Format

Example

Temperature

Two decimal places implied

A value of 1342 would be

equivalent to 13.42°C

Pressure

No decimal places implied for SI
units (kPa) and one decimal

place implied for U.S. units (psi).

A value of 200 would be

equivalent to 200kPag

Differential Pressure

Two decimal places implied for
inches of H2O and 3 places for

kPa

A value of 35142 would be

equivalent to 35.142kPa

Density (kg/m3)

One implied decimal place

A value of 5137 would be

equivalent to 513.7 kg/m3

Density (Relative Density)

Four implied decimal places

A value of 10023 would be

equivalent to 1.0023 60F/60F.

Density (API)

Two implied decimal places

A value of 8045 would be
equivalent to 80.45 °API.


When selecting the 4 to 20mA process input scaling, the module uses the

following ranges:

4 to 20mA

Processor

Module

0%

100%

SLC

MVI46-AFC

3277

16384

ControlLogix

MVI56-AFC

13107

65535

CompactLogix

MVI69-AFC

6241

31206

PLC

MVI71-AFC

819

4095

Quantum

PTQ-AFC

4000

20000


The module uses the configured values for zero and full scale to interpret the

process input scaling.
In the Meter Monitor window, the raw values as transferred from the processor

are shown at the "Last Raw" column and the converted values are shown at the

"Scaled Avg" column.