Modbus Communication

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 80 of 316

ProSoft Technology, Inc.

February 25, 2011

6.3

Modbus Master

Port 3 can be configured for Modbus Master operation (Project / Site
Configuration / Port 3
).

The Modbus Master command is generated from the processor using ladder

logic (Modbus master block). After the Modbus Master transaction is completed

the module is ready to receive another Modbus Master request from the ladder

logic:

The following Modbus functions are supported for Modbus Master operation:

Modbus Function Code

Description

1

Read Coil Status

2

Read Input Status

3

Read Holding Registers

4

Read Input Registers

15

Force (Write) Multiple Coils

16

Preset (Write) Multiple Registers


The module offers considerable flexibility for Modbus Master operation, allowing

the ladder logic to select one of the following data types:
 Bit (packed 16 to a word)
 Word (16-bit register)
 Long (32-bit items as register pairs)
 Long Remote (32-bit items as single registers)

Note: Long data type implements each data unit as one pair of 16-bit registers (words). Each
register contains two bytes. Long remote data type implements each data unit as one 32-bit
register. Each register contains four bytes. The proper choice depends on the remote slave’s
Modbus implementation.