MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Backplane Communication

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 193 of 316

February 25, 2011

Description
This block returns an archive record to the PLC, selected according to the criteria

in the Output block. Archive fetch may be controlled through the use of the

"ignore output" bit (bit 8) of the block id; the "skip input" bit (bit 9) has no function

and is ignored.

Output block format:

Word

Description

1

Archive file select; 0 daily, 1 hourly

2

Age of requested archive

3 to 41

[ignored]

Input block format:

Word

Description

1

Error bitmap:
Bit 0: Archive file selection invalid
Bit 1: Age outside configured file size

2 to 41

Archive record data (up to 40 words, or 0 on error

11.2.11 Function Block Definition - 16/17/18/19: Modbus Gateway

Read

Output Function Block ID
Function Code 16: Read Modbus Registers from the PRIMARY Slave
HOLDING register bank.

Function Code 17: Read Modbus Registers from the VIRTUAL Slave HOLDING
register bank.