ProSoft Technology MVI56-AFC User Manual

Page 243

Advertising
background image

MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Sample Logic

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 243 of 316

February 25, 2011

The valid Modbus error codes are listed below:

Error

Description

=0

No error

>0

Modbus exception code or communication error
Modbus exception codes are issued by the responding slave and listed in

commonly available Modbus protocol manuals; they lie between 1 and 127,

and include:

1

Illegal function

2

Illegal address

3

Illegal data value

Communication errors are issued by the AFC:

Error

Description

500

CTS timeout

501

Receive timeout

502

Bad framing

503

Buffer overrun

504

Bad checksum/CRC

505

Wrong slave

506

Wrong function code

507

Wrong length

<0

Configuration, parameter, or logic error:

-1

Master Port not configured

-2

Master Port never used

-3

Bad Slave Address

-4

Bad Direction/Target

-5

Bad Datum Size/Swap Options

-6

Bad number of data items

Advertising
This manual is related to the following products: