ProSoft Technology MVI56-AFC User Manual

Page 284

Advertising
background image

Reference

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 284 of 316

ProSoft Technology, Inc.

February 25, 2011

14.4.1 Information for Users of AFC Manager Versions Older Than

2.01.000

If you are using AFC Manager versions older than 2.01.000, you must set these

bits using the Modbus master interface in the AFC Manager. Please refer to the

AFC Manager User Manual for further information about the Modbus Master

interface feature.
Refer to the following words to configure the archive options directly to the

Modbus database:

Address

Description

8341

Meter 1 daily archive configuration word

8421

Meter 1 hourly archive configuration word

10341

Meter 2 daily archive configuration word

10421

Meter 2 hourly archive configuration word

12341

Meter 3 daily archive configuration word

12421

Meter 3 hourly archive configuration word

14341

Meter 4 daily archive configuration word

14421

Meter 4 hourly archive configuration word

16341

Meter 5 daily archive configuration word

16421

Meter 5 hourly archive configuration word

18341

Meter 6 daily archive configuration word

18421

Meter 6 hourly archive configuration word

20341

Meter 7 daily archive configuration word

20421

Meter 7 hourly archive configuration word

22341

Meter 8 daily archive configuration word

22421

Meter 8 hourly archive configuration word

Each archive configuration word has the following bitmap structure:

Bit

Description

0

Period select, hourly

1

Archive upon period end

2

Archive upon event

3

Reserved

4

Reset resettable accumulator 1 upon period end

5

Reset resettable accumulator 2 upon period end

6

Reset resettable accumulator 3 upon period end

7

Reset resettable accumulator 4 upon period end

8

Reset resettable accumulator 1 upon event

9

Reset resettable accumulator 2 upon event

10

Reset resettable accumulator 3 upon event

11

Reset resettable accumulator 4 upon event

12

Reserved

13

Reserved

14

Reserved

15

Reserved

Note: Bit 0 must be set only for the hourly archives.

Advertising