Diagnostics and Troubleshooting

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 258 of 316

ProSoft Technology, Inc.

February 25, 2011

13.3 Meter Alarms

If the module is generating unexpected data, you should verify if the meter has

any alarms. Some alarms may be caused by an issue that could potentially affect

the calculation results. Each archive also keeps track of the alarms that have

occurred during the period (refer to the Archive section). The Meter Monitor

dialog box allows you to monitor the meter alarms.

The above image shows the Meter Alarms bitmap, which gives you a quick

overview of active alarms. Associated with many of these bits are Alarm Code

registers which supply specific reasons for the alarms, most of which appear in

the lower right corner of the main Meter Monitor window. For complete

information, including which Code registers are associated with which alarm bits,

use the Modbus Dictionary feature of AFC Manager.
The possible alarms are listed in the following table. Of the Alarm Codes listed,

the values that can actually appear depend on both the selected Product Group

and the firmware version.

Alarm Message

Description

Solution

Accumulation

Overflow

The module ignores an accumulator
increment of less than zero or greater
than 1.000.000.000 occurring in a

single meter scan.

Check your meter configuration to
verify if your project is generating

reasonable values.

Analysis Total Not
Normalized (v ≤

2.04)

Absolute difference between analysis
total and 1.0000 (100%) is greater

than the error tolerance

Make sure that the sum of all molar
concentrations is within the error

tolerance of 1.0000 (100%).