MVI56-AFC ♦ ControlLogix Platform

Meter Channel Functionality

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 33 of 316

February 25, 2011

3.2

Linear (Pulse) Meter Overview

The module typically receives the pulse count and pulse frequency values from a

high-speed counter module. The module uses these values to perform

calculations.
You can configure the primary input to be used for volume calculation. You can

configure it as Pulse Count or Pulse Frequency.

3.2.1 Primary Input = Pulse Count

If you select Pulse Count as the primary input, the module uses the pulse count

value transferred through the backplane as the primary input for volume

calculation. In this case, the pulse frequency will be used for flow rate calculation

only.

3.2.2 Primary Input = Pulse Frequency

If you select Pulse Frequency as the primary input, the module uses the pulse

frequency value transferred through the backplane as the primary input for both

flow accumulation and flow rate calculation. The pulse count value is ignored by

the module.