MVI56-AFC ♦ ControlLogix Platform

Meter Proving

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 65 of 316

February 25, 2011

The Latest Prove Results is a block of 1310 registers, starting at input register

62400 and proceeding through register 63709. The table below explains these

sub-areas.

Name

Module Memory
Address

Description

Prove Status

62400 to 62409

Occupies 10 registers

Prove Setup

62410 to 62553

Occupies 140 registers and protects meter
configuration and prove setup information

for use by proving calculations and report

generation; this information remains
unchanged from the moment of enable,

regardless of how the original source

information might be altered during or after

the prove

Prove Acceptance

62554 to 62575

Occupies 22 registers and records
timestamps associated with the prove,

accumulator totalizer values, and details of

the disposition of the new meter factor upon

acceptance of the prove.

Prover Configuration

62576 to 62655

Occupies 80 registers and has the same
purpose as Prove Setup, to protect the
prover configuration against subsequent

changes so that proving can proceed under

reliably constant parameters, and so that the

proving report can be generated and
regenerated according to the original

conditions of the prove.

Prove Only Calculations

62656 to 62665

Occupies 10 registers and contains a few
calculated values that are applicable only for

the prove as a whole.

Reading and Calculations for

Prove

62666 to 62781

Occupies 116 registers and the "readings"
part contains the averages of the

corresponding readings for all runs of the
prove. The "calculations" part contains

calculations performed upon the prove-level

readings if calculation method "average

data" was chosen.

Reading and Calculations for

Runs

62782 to 63709

Occupies 166 registers for each of up to 8

runs of the prove. The layout of each block
of 116 registers is identical to that of the

Readings and Calculations for Prove block.

The "readings" part contains the weighted

averages or snapshots of all process input
and counter card input for the duration of the

run. The "calculations" part contains

calculations performed upon the run-level

readings if calculation method "average

meter factor" was chosen.