MVI56-AFC ♦ ControlLogix Platform

Events

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 141 of 316

February 25, 2011

9.8

Special Events

Tag

Rkv

Description

0

-

Never Used
Value: Always 0.
Notes: This entry in the Event Log has never been written.
The number of such entries starts at 1999 upon cold start and

decreases as events are written until none remain, after which oldest

events are overwritten with new ones.

1

-

Event Log Download
Value: Number of last-downloaded event.
Notes: Triggered by a purge of the Event Log, which marks older events

as available to be overwritten by new ones.

2

-

Cold Start
Value: Always 0.
Notes: This event is obsolete and is never written.

3

(1)

Power-Up
Value: "Old" value is the last-saved wallclock from the previous session;

"new" value is always 0 (clock not yet set).
Notes: The last event written upon restart of the application and before

entering the meter scan. This event may be preceded by Checksum

Alarm and/or PLC Mode Change events.

4

-

PLC Mode Change
Value: PLC mode (0 on line, 1 off line).
Notes: Logs changes to PLC connectivity as reported by the backplane

procedures. Typically caused by switching the PLC between "run" and

"program" modes.

5

-

Checksum Alarm
Value: Checksum alarm word (datum type "Bsht").
Notes: Logs changes to the checksum alarm bitmaps.
Includes site/meter identification (bits 28-24).
Upon power-up:
Written automatically upon power up when a checksum failure is
detected. In this case the event is written even if the bitmap does not

change, such as when an affected bit is already set from a previous

failure that was never cleared.
Upon Modbus write to the bitmap:
Records changes to the bitmap only, typically when clearing bits, though

setting bits is also permitted.

6

(2)

Wallclock Change
Value: Wallclock (packed bitfields).
Notes: Triggered when the wallclock is set for the first time, or when it is

reset to a value that differs from its current value by five minutes or

more. These two cases can be distinguished by the "old value" in the

event entry: for the initial setting this value is zero ("clock not set").

7

*

Stream Select
Value: Stream number.
Notes: Triggered by a "select active stream" meter signal.
Includes meter identification (bits 28-24).