14.5 Archive Data Format

There are 3 columns associated with each archive data:

Column

Description

Ofs

Shows the offset location of the data in each archive. The maximum offset value

will depend on the Record Size value you configured.
If the value has a "+" value (for example 0+) it means that the data occupies 2

words of data.

Reg

Shows the Primary Modbus Slave Address of the data. This is a meter-relative
address. For example: a Reg value of 890+ for meter 1 would be equivalent to

Modbus addresses 8890 and 8891.

Description

Data Description.

14.5.1 Timestamp Date and Time Format

The date and time format used in the archives is stored in a highly compressed

form in order to represent the date and time using only 2 words of data:

Word

Description

0

Date

1

Time

In order to extract the information from the date format use the following

arithmetic:

Date Word
Year = ([Bits 15 thru 9] from Word 0) + 1996
Month = ([Bits 8 thru 5] from Word 0) + 1
Day = ([Bits 4 thru 0] from Word 0) + 1

Time Word
Hour = ([Bits 15 thru 11] from Word 1)
Minute = ([Bits 10 thru 5] from Word 1)
Second = ([Bits 4 thru 0] from Word 1 )* 2