MVI56-AFC Sample Logic

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 206 of 316

ProSoft Technology, Inc.

February 25, 2011

12.1 Sample Logic Overview

The logic basically sends output blocks to the MVI56-AFC and receives the input

blocks from the module. Each block contains a Block Sequence number that

identifies the block. The input response block sent by the module will also contain

the same Block Sequence Number as the previous output block.

The ladder logic performs the following sequence:
1 Receives the input block from the MVI56-AFC
2 Copies the input block content from the input buffer to the controller tags

based on the Block Sequence Number

3 Increments the next Block Sequence Number
4 Builds the next output block with the new Sequence Number
5 Sends the new output block to the module.