Meter Proving

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 46 of 316

ProSoft Technology, Inc.

February 25, 2011

Master Meter
This proving technique proves a meter by comparing its behavior to that of

another master meter whose behavior is deemed to be accurate. A master meter

itself must be proved to a high precision by using a conventional prover.

4.1.2 Prover Options

There are several options affecting the handling and representation of data, as

well as affecting the relevance and availability of some configuration items. Not

all options are available for all prover types. If an option does not apply to a

particular prover type, it cannot be selected. For a description of each option

listed below see the corresponding Modbus dictionary address in parenthesis

below.

 Dual transmitters, temperature (65011.0)
 Dual transmitters, pressure (65011.1)
 Input meter density (65011.2)
 Return leg pulse count is round –trip count (65011.4)
 Prover is double-walled (65011.5)
 External switch bar (65011.6)
 Calculation method: Average Meter Factor (else Average Data) (65011.8)