MVI56-AFC ♦ ControlLogix Platform

Events

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 139 of 316

February 25, 2011

9.6

Period-end Events

A "period-end" event is detected by the wallclock. There are two such:

a) "End-of-hour" occurs when the minute of the hour steps into the "End-of-

hour minute" of Site Configuration.

b) "End-of-day" occurs when the minute of the day steps into the "End-of-day

minute" of Site Configuration.

A wallclock change that skips forward over an end-of-period minute will cause

that period-end to be missed, and a change that skips backward over that minute

will cause that period-end to be repeated, so wallclock adjustments should be

performed at times well-removed from either end-of-period minute.
Though a period-end event is not recorded in the event log, it does cause

archives and resets to be scheduled for all enabled meters according to their

configured "period-end" Archive Options. Archives and resets scheduled by

period-end are delayed in their action until at least one meter scan has occurred

after the event (the archive data accumulation that takes place at the end of the

meter scan also records the latest timestamp, so the written archive then reflects

the fact that the period-end has occurred).