The user should configure the following parameters for the command to be sent:

Parameter

Use this Controller Tag

Description

Enable

AFC56.ModbusMaster.Command[0].
Outp
ut.Config.Enable

This value should be set as 1 in
order to enable the command. If

this value
is 0 the module will ignore the

Modbus master command

Function Type

AFC56.ModbusMaster.Command
[0].Output.Config.FunctionType_Write

0 = Read from Modbus slave
1 = Write to Modbus slave

Register Bank

AFC56.ModbusMaster.Command
[0].Output.Config.RegisterBank_Input

0 = Holding Register
1 = Input Register

Data Type = Bit AFC56.ModbusMaster.Command

[0].Output.Config.DataType.Bit

0 = Don't use bit
1 = Use bit

Data Type =

Word

AFC56.ModbusMaster.Command
[0].Output.Config.DataType.Word

0 = Don't use word
1 = Use word

Data Type =

Long

AFC56.ModbusMaster.Command
[0].Output.Config.DataType.Long

0 = Don't use long
1 = Use long

Data Type =

Long Remote

AFC56.ModbusMaster.Command
[0].Output.Config.DataType.LongRemote

0 = Don't use long remote
1 = Use long remote

Swap Bytes

AFC56.ModbusMaster.Command
[0].Output.Config.SwapOptions.SwapBytes

0 = Don't swap bytes
1 = Swap bytes
(Not valid for bits)

Swap Words

AFC56.ModbusMaster.Command
[0].Output.Config.SwapOptions.
SwapWords

0 = Don't swap words
1 = Swap words
(Not valid for bits or words)

Slave Address

AFC56.ModbusMaster.Command
[0].Output.Config.SlaveAddress

Modbus slave address

Modbus Address AFC56.ModbusMaster.Command

[0].Output.Config.ModbusAddress

Register address in the Modbus

slave

Element Count

AFC56.ModbusMaster.Command
[0].Output.Config.ElementCounts

Number of elements to be

transferred

Transaction

Number

AFC56.ModbusMaster.Command[0].
Output.TransactionNumber

This number will be echoed in the
input block. It allows to multiplex

more than one command in the

same logic.


The following variables are automatically built by the ladder logic and the user

does not have to modify these values:
AFC56.ModbusMaster[0].Output.Config.Type_Swap