ProSoft Technology MVI56-AFC User Manual

Page 74

Advertising
background image

Modbus Database

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 74 of 316

ProSoft Technology, Inc.

February 25, 2011

5.3

Virtual Slave

The module also provides a Virtual Address Space of 20,000 Modbus registers.

This address space is divided equally between the Input Register Bank (10,000

registers) and the Holding Register Bank Holding Register Bank (10,000). This is

where you can create a virtual re-map by cross-referencing any of the 130,072

Primary Slave Modbus registers to the 20,000 Modbus registers in the Virtual

Slave Banks, thereby making it easy for a SCADA Master to poll only the

necessary Modbus addresses in contiguous blocks. The virtual slave can also be

used for data polling from the processor through the backplane.
Modbus access to the Virtual Modbus Slave is disabled by default since its

Modbus address is originally set as 0. To use the Virtual Modbus Slave, you

must initially configure a Modbus address greater than zero in order to enable it.

Refer to Site Configuration for more information about enabling the Virtual Slave

and using the remapping feature. The PLC may always access the Virtual Slave,

whether or not it has a non-zero slave address and thus is available via Modbus.
A download operation will not transfer the Virtual Slave Remapping configuration.

You must click on the Write button on the Indirect Address Remapping dialog

box to transfer the data.

Note: The first 100 registers in the Virtual Slave Holding Register Bank have been pre-assigned
and cannot be remapped. They map directly to the first 100 holding registers of the Primary Slave.

Advertising
This manual is related to the following products: