12.3.5 Meter Profile

The logic constantly reads each meter profile. The meter profile informs each

meter type (linear or differential), product group (gas or liquid) and currently

selected stream (1 through 4).
The AFC56.Meters[x].Profile controller tag stores the profile information for each

meter run:
AFC56.Meters[0].Profile - Meter 1 Profile
AFC56.Meters[1].Profile - Meter 2 Profile
...
AFC56.Meters[15].Profile - Meter 16 Profile
The controller tags are interpreted as follows:

Controller Tag

Value

Description

AFC56.Meters[x].Profile.MeterType

0

Meter x is Differential Meter

AFC56.Meters[x].Profile.MeterType

1

Meter x is a Linear Meter

AFC56.Meters[x].Profile.ProductGroup

0

Meter x uses a Gas product

AFC56.Meters[x].Profile.ProductGroup

1

Meter x uses a Liquid product

AFC56.Meters[x].Profile.SelectedStream

1

Stream 1 is currently selected (active)

AFC56.Meters[x].Profile.SelectedStream

2

Stream 2 is currently selected (active)

AFC56.Meters[x].Profile.SelectedStream

3

Stream 3 is currently selected (active)

AFC56.Meters[x].Profile.SelectedStream

4

Stream 4 is currently selected (active)

The example below shows a situation where Meter 0 is configured as a linear

meter and uses a gas product.