9.13 "Rkv" Notes

1 Archives (only, not resets) are forced regardless of configuration, capturing

any unarchived data from the previous session.

2 Archives and resets are scheduled (immediately, without a "period-end"

delay) only for the initial setting of the wallclock; a "five-minute" event causes

no scheduling. This ensures capture of any flow that has occurred prior to the

initial clock-set.

3 Event occurs only when one or more of the following bits are changed:

o

Bit 2, "Barometric pressure units"

o

Bit 5, "Process input out of range use last good"

o

Bit 12, "Analysis is packed in module"

o

Bit 13, "Analysis is packed over backplane" (1756 and 1769 platforms

only)

4 A change to Meter Control Options bit 15, "Meter enable", imposes these

adjustments to the normally-scheduled archives/resets:

o

Upon meter enable, cancel any scheduled archives (no data yet to be

archived), but leave in place any scheduled resets.

o

Upon meter disable, cancel any resets (for inspection and so on.; reset

will be rescheduled upon subsequent enable), and force archiving of both

files regardless of configuration (so that a disabled meter never has any

pending unarchived data).

5 Events occur only if Meter Control Options bit 10, "Treat analysis as process

input", is clear.