Diagnostics and Troubleshooting

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 262 of 316

ProSoft Technology, Inc.

February 25, 2011

13.4 Checksum Alarms

A checksum alarm indicates a checksum verification failure during power-up.

Non-volatile information is kept in battery-backed RAM. It is partitioned into

several blocks, each of which contains a checksum, and when the information is

changed the checksum is updated also. During power-up, the checksum is

verified, and upon failure the alarm bit is latched and the checksum corrected.
The alarm bit remains latched, even through subsequent power cycles, until it is

explicitly cleared from an external source such as the AFC Manager. Refer to the

AFC Manager User Manual for more information about this feature.