MVI56-AFC Backplane Communication

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 166 of 316

ProSoft Technology, Inc.

February 25, 2011

The controller may then verify the validity of the returned data by checking that

the received sentinel echo is the same as the anchor echo. If more than one

OBA is being processed, the transaction number must be used to match the IBA

(AFC output) with the originating OBA (AFC input, controller output).

Input Block Length and Format Alarm
The "length" element returned by the module in the IBA has the high-order (sign)

bit set if any formatting error is detected in the data portion of the OBA you

formatted in the logic. This is referred to as a "format alarm". The remainder of

the input length element contains the number of data words successfully

processed before any formatting inconsistencies were detected by the AFC

module and the alarm condition annunciated. If no formatting error exists, the

length element will echo the output length you entered. If the output length

element itself raises an alarm (for example, value > 245), then the returned

length value is -1.